Field Tests of Active Power Filter (APF)
An active power filter (APF) was built by cooperation between power electronics lab of UM and Tsinghua University. The APF was installed in the feeder for the main square of the Gymnasium of University of Macau during Nov. 20th to Dec. 20th, 2007 for testing. The total harmonic distortion of the source currents reduce from 20% to around 9%. The reactive power and neutral currents are also compensated simultaneously by the AFP.
CPLD-implemented Soft-Switching for Two-Level Inverter --- Hardware prototypes and testing results
CPLD | ||
CPLD-implement soft-switching for two-level inverter |
Two-Level Active Power Filter (APF) --- Established by University of Macau & parallel part of the UPQC
Two-level active power filter (APF) | Two-level voltage source inverter for the filter |
Compensation of the current harmonics and neutral current
After compensation |
Before compensation |
Compensation of the reactive power and harmonics
Before compensation |
After compensation
Dynamic Voltage Restorer (DVR) --- Jointly established by Tsinghua University and University of Macau & series part of the UPQC
Dynamic voltage restorer (DVR) | DVR response time |
Compensation of voltage fluctuation | Compensation of voltage sag | |
Before compensation | ||
After compensation | ||