PRINCIPLES OF DESIGN OF WATER SUPPLY



•    Plumbing fixtures and appurtances should be supplied with water in sufficient volume and at pressures adequate to function satisfactorily and without undue noise under all circumstances.
•    The design of pipe should be made so that there is no contact between the lines feeding to the cistern or any such other appliance with those feeding water for human consumption.
•    Pipe network should be completely water tight and also remain undamaged either by traffic loads, vibrations or temperature and any strains of buildings.
•    Pipe network in the premises should be optimum discharge of water is obtained consistent with economy.  The system should be free from water hammer, corrosion and should also look aesthetic. 
•    The pipe network should be laid and fixed that it doe not pass by the side of any sewage line or refuse drain nor does it pass through any field of foul ground where dirt or city have been deposited and manure dumps.
•    The pipe network should be laid and fixed so that it shell be accessible at any time for attending to damages, leakages etc.
•    The pipe network should be of adequate size to give the desired rate of flow
•    The pipe network should be divided into sections to facilitate repairs. zzThese section should be separated by valves in order that a section can be isolated for repairs keeping the rest of the distribution.
•     The methods of joining pipe should be such as to avoid water loses.
•    Whenever the pipes are bent it should be so made that these are not likely to materially diminish or alter cross section.
•    The piping should be so laid that air locks do not occur and it should be possible to flush out the network from time to time.
•    The pipes to carry satisfactory and un satisfactory water should be laid separately .whenever a supply of less satisfactory water and satisfactory water has to mixed, which shall be done only by discharging both the flows in to a cistern and by a pipe discharging in to the air gap above t he top level of the cistern at the height equal to twice its nominal bore and in no case less than 15cm.  It is necessary to maintain a definite air gap in all plumbing used in the water closet.

•    In the building if a provision is required to be made for storage of water on account of

1.    In the interruption of supply

2.    to maintain a reserve supply

3.    to regulate discharge in the mains

4.    to maintain a reserve for fire fighting arrangements, a tank for storage of water should be provided which should be watertite and also should be of sufficient thickness and capacity.  The storage reserve should be dust prove and mosquito-proof.  Each storage tank should be easily accessible and placed in such a position as to facilitate thorough inspection and cleaning.  Stagnation of water within the tank is to be avoided.  The tank should be so arranged as to have periodical cleaning done without seriously interfering with the supply of water.  It is to be understood that water when it is stagnant is likely to become a good breeding ground for various organisms which are very dangerous for human beings.  Therefore water tanks are require to be periodically cleaned and after cleaning properly disinfected.

       In the case of underground tanks the contamination of stored water on account of above ground flow and due to seepage of underground water should be avoided.  Whenever underground tanks are required for fire fighting purposes, the same should be approachable easily by fire tenders.  The water which is required for fire fighting is so provided that everyday it gets renewal through an inflow of fresh water supply.

Lead piping should not be utilized anywhere in the domestic water supply system.

Polythene and PVC pipes should not be installed near hot water pipes or near any source of heat.


The dead ends in the pipe lines should be avoided to the extent possible.  The mains should be arranged in a grid formation or network fashion.  Where dead ends are unavoidable, a hydrant should be provided as a washout as the deposition of solids is at a higher rate in the case of dead ends where water stagnates requiring cleaning of pipe lines at frequent intervals.

The wash hydrant should connect to an effectively trapped chamber to avoid contamination.  It should not discharge directly into a sewer line or a manhole or chamber on sewer line.

Air valves should be provided at all summit and washout at low points. The pipeline may follow the general contours of the land. It should be so laid that it generally rises to air walls to a water washout. Care should be maintained positive pressure at every point in the pipe line under normal working conditions.

The mains should be laid at least 90cms below surface under load and atleast 75cms below under a foot path to protect it from various traffic loads coming on it.  Otherwise, there are chances of pipe settling under load and breaking.

Safety demands that water pipe should be separated from electric, telephone and other such cable no piping should be so laid as to pass into or through any sew line or manhole pit, as pit or any material of such nature that it is likely to cause undue deterioration of pipe.

Where laying of any pipe through corrosive soil or environment is inevitable, the piping should be properly protected from contact with such conditions by being carried through
Cast iron tubes or some other suitable means.

Changes in diameter of pipe or changes in direction pipe should be gradual and not abrupt.  Abrupt changes involve avoidable lose of head of water.

No boiler for generating steam or closed boiler of any description or any such machinery should be directly connected with supply pipe.  Every such boiler or machinery should be supplied from a feed tank.

The design of pipe work should be such that there is no possibility back flow from any cistern or appliance whether by siphonage or otherwise. Non return valve should not be relied upon to prevent such back flow.

Where pipe network has to be laid in a recent fill, proper precautions have to be taken to provide continuous and even support.

1 comment:

  1. Interesting and very useful article. It's a great concept of design drinking water information. Safety requirements that water pipe should be split up from electric, phone and other such cable no pipes should be so set as to complete into or through any stitching line, as gap or any product of such characteristics that it is likely to cause excessive destruction of pipe. The water which is required for fire battling is so supplied that daily it gets restoration through an influx of fresh drinking water. Country Reports

    ReplyDelete

Labels

PROJECTS 8086 PIN CONFIGURATION 80X86 PROCESSORS TRANSDUCERS 8086 – ARCHITECTURE Hall-Effect Transducers INTEL 8085 OPTICAL MATERIALS BIPOLAR TRANSISTORS INTEL 8255 Optoelectronic Devices Thermistors thevenin's theorem MAXIMUM MODE CONFIGURATION OF 8086 SYSTEM ASSEMBLY LANGUAGE PROGRAMME OF 80X86 PROCESSORS POWER PLANT ENGINEERING PRIME MOVERS 8279 with 8085 MINIMUM MODE CONFIGURATION OF 8086 SYSTEM MISCELLANEOUS DEVICES MODERN ENGINEERING MATERIALS 8085 Processor- Q and A-1 BASIC CONCEPTS OF FLUID MECHANICS OSCILLATORS 8085 Processor- Q and A-2 Features of 8086 PUMPS AND TURBINES 8031/8051 MICROCONTROLLER Chemfet Transducers DIODES FIRST LAW OF THERMODYNAMICS METHOD OF STATEMENTS 8279 with 8086 HIGH VOLTAGE ENGINEERING OVERVOLATGES AND INSULATION COORDINATION Thermocouples 8251A to 8086 ARCHITECTURE OF 8031/8051 Angle-Beam Transducers DATA TRANSFER INSTRUCTIONS IN 8051/8031 INSTRUCTION SET FOR 8051/8031 INTEL 8279 KEYBOARD AND DISPLAY INTERFACES USING 8279 LOGICAL INSTRUCTIONS FOR 8051/8031 Photonic Transducers TECHNOLOGICAL TIPS THREE POINT STARTER 8257 with 8085 ARITHMETIC INSTRUCTIONS IN 8051/8031 LIGHTNING PHENOMENA Photoelectric Detectors Physical Strain Gage Transducers 8259 PROCESSOR APPLICATIONS OF HALL EFFECT BRANCHING INSTRUCTIONS FOR 8051/8031 CPU OF 8031/8051 Capacitive Transducers DECODER Electromagnetic Transducer Hall voltage INTEL 8051 MICROCONTROLLER INTEL 8251A Insulation Resistance Test PINS AND SIGNALS OF 8031/8051 Physical Transducers Resistive Transducer STARTERS Thermocouple Vacuum Gages USART-INTEL 8251A APPLICATIONs OF 8085 MICROPROCESSOR CAPACITANCE Data Transfer Instructions In 8086 Processors EARTH FAULT RELAY ELECTRIC MOTORS ELECTRICAL AND ELECTRONIC INSTRUMENTS ELECTRICAL BREAKDOWN IN GASES FIELD EFFECT TRANSISTOR (FET) INTEL 8257 IONIZATION AND DECAY PROCESSES Inductive Transducers Microprocessor and Microcontroller OVER CURRENT RELAY OVER CURRENT RELAY TESTING METHODS PhotoConductive Detectors PhotoVoltaic Detectors Registers Of 8051/8031 Microcontroller Testing Methods ADC INTERFACE AMPLIFIERS APPLICATIONS OF 8259 EARTH ELECTRODE RESISTANCE MEASUREMENT TESTING METHODS EARTH FAULT RELAY TESTING METHODS Electricity Ferrodynamic Wattmeter Fiber-Optic Transducers IC TESTER IC TESTER part-2 INTERRUPTS Intravascular imaging transducer LIGHTNING ARRESTERS MEASUREMENT SYSTEM Mechanical imaging transducers Mesh Current-2 Millman's Theorem NEGATIVE FEEDBACK Norton's Polarity Test Potentiometric transducers Ratio Test SERIAL DATA COMMUNICATION SFR OF 8051/8031 SOLIDS AND LIQUIDS Speed Control System 8085 Stepper Motor Control System Winding Resistance Test 20 MVA 6-digits 6-digits 7-segment LEDs 7-segment A-to-D A/D ADC ADVANTAGES OF CORONA ALTERNATOR BY POTIER & ASA METHOD ANALOG TO DIGITAL CONVERTER AUXILIARY TRANSFORMER AUXILIARY TRANSFORMER TESTING AUXILIARY TRANSFORMER TESTING METHODS Analog Devices A–D BERNOULLI’S PRINCIPLE BUS BAR BUS BAR TESTING Basic measuring circuits Bernoulli's Equation Bit Manipulation Instruction Buchholz relay test CORONA POWER LOSS CURRENT TRANSFORMER CURRENT TRANSFORMER TESTING Contact resistance test Current to voltage converter DAC INTERFACE DESCRIBE MULTIPLY-EXCITED Digital Storage Oscilloscope Display Driver Circuit E PROMER ELPLUS NT-111 EPROM AND STATIC RAM EXCITED MAGNETIC FIELD Electrical Machines II- Exp NO.1 Energy Meters FACTORS AFFECTING CORONA FLIP FLOPS Fluid Dynamics and Bernoulli's Equation Fluorescence Chemical Transducers Foil Strain Gages HALL EFFECT HIGH VOLTAGE ENGG HV test HYSTERESIS MOTOR Hall co-efficient Hall voltage and Hall Co-efficient High Voltage Insulator Coating Hot-wire anemometer How to Read a Capacitor? IC TESTER part-1 INSTRUMENT TRANSFORMERS Importance of Hall Effect Insulation resistance check Insulator Coating Knee point Test LEDs LEDs Display Driver LEDs Display Driver Circuit LM35 LOGIC CONTROLLER LPT LPT PORT LPT PORT EXPANDER LPT PORT LPT PORT EXTENDER Life Gone? MAGNETIC FIELD MAGNETIC FIELD SYSTEMS METHOD OF STATEMENT FOR TRANSFORMER STABILITY TEST METHODS OF REDUCING CORONA EFFECT MULTIPLY-EXCITED MULTIPLY-EXCITED MAGNETIC FIELD SYSTEMS Mesh Current Mesh Current-1 Moving Iron Instruments Multiplexing Network Theorems Node Voltage Method On-No Load And On Load Condition PLC PORT EXTENDER POTIER & ASA METHOD POWER TRANSFORMER POWER TRANSFORMER TESTING POWER TRANSFORMER TESTING METHODS PROGRAMMABLE LOGIC PROGRAMMABLE LOGIC CONTROLLER Parallel Port EXPANDER Paschen's law Piezoelectric Wave-Propagation Transducers Potential Transformer RADIO INTERFERENCE RECTIFIERS REGULATION OF ALTERNATOR REGULATION OF THREE PHASE ALTERNATOR Read a Capacitor SINGLY-EXCITED SOLIDS AND LIQUIDS Classical gas laws Secondary effects Semiconductor strain gages Speaker Driver Strain Gages Streamer theory Superposition Superposition theorem Swinburne’s Test TMOD TRANSFORMER TESTING METHODS Tape Recorder Three-Phase Wattmeter Transformer Tap Changer Transformer Testing Vector group test Virus Activity Voltage Insulator Coating Voltage To Frequency Converter Voltage to current converter What is analog-to-digital conversion Windows work for Nokia capacitor labels excitation current test magnetic balance voltage to frequency converter wiki electronic frequency converter testing voltage with a multimeter 50 hz voltages voltmeter