ISO Modules
Electrically Insulated Signal Conversion and Conditioning,
Temperature Measurement, and Signal Combination
- ISO-FIL Module Signal Converter for Voltage and Current
Electrically insulated low noise signal converter for voltage and current signals - ISO-TC Module Amplifiers for Thermocouples
Electrically insulated acquisition of temperature values with thermocouples - ISO-PT Module Amplifiers for Pt100
Electrically insulated acquisition of temperature values with Pt100 - ISO-Strain-Gauge Amplifiers for Strain Gauge Bridges
Conditioning measurement signals from strain gauge bridges with resistances ranging from 350 to 1,000 ohms. Integrated sensor power supply - ISO-Poti Module Amplifiers for Potentiometer
Conditioning measurement signals of potentiometer sensors. Integrated power supply - ISO-DC Module Differential Insulated Measurement of DC Voltage
Differential measuring of voltage and shunt sensor current - ISO-ICP Module Insulated Amplifier for ICP® Sensors
Electrically insulated conditioning of ICP® sensors. Integrated current supply of 4 mA - ISO-RMS Module Amplifier for RMS Output
Electrically insulated signal conditioning with RMS signal output - ISO-IF Module Insulated Pulse Forming
Electrically insulated pulse forming of rotational signals from speed counters, Hall generators, incremental counters, etc. - ISO-Math Module Insulated Amplifier for Arithmetic Functions
Electrical combination of two signal voltages, and arithmetic calculation of values
All modules have the following features:
- Flexible filtering characteristics through plug-in filters (suppression of interferences, anti-aliasing, frequency limitation)
- Comes with one low-pass filter (standard frequency)
- Standard frequencies (Butterworth or Bessel filter, 4th order): 10, 30, 50, ..., 3k, 5k, 10k [Hz]
- 5 kHz Butterworth, if not otherwise specified (other filters in 4th or 8th order on request)
- Extremely low-noise, typical residual ripple 2 mVpp
- Accuracy 0.1%
- 3-way insulation
- Electrical insulation 1,000 V DC
- Supply voltage 24 V DC (12 V on request)
- DIN-rail mounting
ISO-FIL Module
Electrically Insulated Transmission and Filtering of Voltage and Current Signals
- Single and bipolar input / output: ± 10 V, 0-10 V, ± 20 mA, 0-20 mA, 4-20 mA
(please specify one configuration with order) - Cut-off frequency max. 10 kHz, standard filter 5 kHz (Butterworth)
- Second voltage output through additional plug-in filter
Detailed information can be found in our PDF file
Electrically Insulated Transmission and Filtering of Voltage and Current SignalsISO-Pt100 Module
Floating input signal conditioning for Pt 100 sensors
- Integrated precise linearisation and sensor current supply 1mA
- 4-wire connection
- Range - 100 ... + 500 °C (others on request)
- Single and bipolar input / output: ± 10 V, 0-10 V, ± 20 mA, 0-20 mA, 4-20 mA
(please specify one configuration with order) - Cut-off frequency standard 10 Hz (Butterworth), max. 5 kHz
- Second voltage output through additional plug-in filter
ISO-TC Module (Thermocouple)
Floating input signal conditioning for thermocouples
- Integrated precise linearisation and cold spot compensation
- Monitoring of wire break
- Thermocouple type J, K (others on request)
- Range - 100 ... + 1,000 °C (others on request)
- Single and bipolar input / output: ± 10 V, 0-10 V, ± 20 mA, 0-20 mA, 4-20 mA
(please specify one configuration with order) - Cut-off frequency standard 10 Hz (Butterworth), max. 1 kHz
- Second voltage output through additional plug-in filter
Detailed information can be found in our PDF file
Temperature Measurement with Pt100 and Thermocouples
ISO-Strain-Gauge Module
Conditioning Measurement Signals from Strain Gauge Bridges
- Resistance values 350 - 1,000 ohms (optional 120 ohms)
- Integrated sensor power supply + 5 V DC
- 4-wire / 6-wire connection
- Range 2, 4, 10 mV/V (other on request)
- Full bridge (optional half bridge)
- Single and bipolar input / output: ± 10 V, 0-10 V, ± 20 mA, 0-20 mA, 4-20 mA
(please specify one configuration with order) - Cut-off frequency max. 10 kHz, standard filter 5 kHz (Butterworth)
- Second voltage output through additional plug-in filter
Detailed information can be found in our PDF file
Conditioning Measurement Signals from Strain Gauge Bridges
ISO-Potentiometer Module
Conditioning Measurement Signals of Potentiometer Sensors
- Integrated sensor power supply + 5 V DC
- 3-wire / 5-wire connection
- Gain: 1, 2, 4, 8
- Single and bipolar input / output: ± 10 V, 0-10 V, ± 20 mA, 0-20 mA, 4-20 mA
(please specify one configuration with order) - Cut-off frequency max. 10 kHz, standard filter 5 kHz (Butterworth)
- Second voltage output through additional plug-in filter
Detailed information can be found in our PDF file
Conditioning Measurement Signals of Potentiometer Sensors - Single and bipolar input / output: ± 10 V, 0-10 V, ± 20 mA, 0-20 mA, 4-20 mA